Installation of thermal alarm signals and automatic protection control for screw air compressor stations
Release time:
2021-08-09
Author:
Source:
Abstract
Serial Number |
Measuring Point Name |
Oil-free Screw |
Oil-injected Screw |
|||
Thermal Alarm Signal |
Automatic Protection |
Thermal Alarm Signal |
Automatic Protection |
|||
I. Temperature |
||||||
1 |
High Exhaust Temperature |
Should |
Automatic Shutdown |
Should |
Automatic Shutdown |
|
2 |
Low Exhaust Temperature |
— |
— |
Should |
— |
|
3 |
High Lubricating Oil Temperature |
Should |
— |
Should |
— |
|
4 |
High Cooling Water Return Temperature |
Should |
— |
Should |
— |
|
II. Pressure |
||||||
1 |
Low Compressed Air Station Supply Main Pressure |
Should |
— |
Should |
— |
|
2 |
High Compressed Air Station Supply Main Pressure |
Should |
— |
Should |
— |
|
3 |
Low Cooling Water Flow or Pressure |
Should |
Automatic Shutdown |
Should |
Automatic Shutdown |
|
4 |
Low Intake Air Pressure |
Should |
— |
— |
— |
|
5 |
Large Oil-Gas Separator Filter Element Differential Pressure |
— |
— |
Should |
— |
|
6 |
Large Oil Filter Differential Pressure |
Should |
— |
Should |
— |
|
7 |
Low Lubricating Oil Pressure |
Should |
Automatic Shutdown |
Should |
Automatic Shutdown |
|
III. Level |
||||||
1 |
Low Lubricating Oil Tank Oil Level |
Should |
— |
Should |
— |
|
2 |
High Lubricating Oil Tank Oil Level |
— |
— |
Should |
— |
|
IV. Other |
||||||
1 |
Air Compressor Unit Control Power Failure |
Should |
— |
Should |
— |
|
Note: 1. An alarm should be triggered when the parameters of the alarm device are abnormal, and automatic shutdown should occur if the alarm value continues to exceed the limit; |