Installation of thermal measurement instruments at the centrifugal air compressor station

Release time:

2021-08-09

Author:

Source:


Abstract

Serial Number

Measuring Point Name

Installation

I. Temperature

1

Inlet Air Temperature of Each Stage

Should

2

Exhaust Air Temperature of Each Stage

Should

3

Lubricating Oil Cooler Inlet Oil Temperature

Should

4

Lubricating Oil Cooler Outlet Oil Temperature

Should

5

Lubricating Oil Tank Oil Temperature

Should

6

Lubricating Oil Cooler Drainage Temperature

Should

7

Water Temperature of the Main Water Inlet Pipe at Each Level

Should

8

Cooling Water Inlet Main Pipe Water Temperature

Should

9

Speed Increaser Bearing Temperature

Should

10

Compressor Bearing Lubricating Oil Temperature

Should

11

Compressor Motor Bearing Lubricating Oil Temperature

Should

12

Compressor and Motor Support Thrust Bearing Temperature

Should

13

Compressor Motor Support Bearing Temperature

Should

14

Compressor Motor Stator Temperature

Should

II. Pressure

1

Cylinder Inlet Air Pressure of Each Stage

Should

2

Cylinder Exhaust Air Pressure of Each Stage

Should

3

Aftercooler Outlet Air Pressure

Should

4

Air Compressor Cooling Water Inlet (After Valve) Pressure

Should

5

Compressed Air Station Supply Air Main Pipe Pressure

Should

6

Lubricating Oil Pump Outlet Main Pipe Oil Pressure

Should

III. Flow Rate

1

Air Compressor Unit Outlet Flow Rate

Should

2

Compressed Air Station Supply Air Main Pipe Flow Rate

Should

IV. Others

1

Compressor Shaft Vibration

Should

2

Compressor Shaft Displacement

Should

3

Speed Increaser Shaft Vibration

Should

Recommended Reading


Applications of low-pressure, high-volume compressed air dryers


The same warehouse transports different raw materials between different countries. In this case, warehouse cleaning becomes the most important link in ensuring that goods are not contaminated.

2021-08-09

Comparison of various suction machine performances


Different adsorption regeneration methods will have differences in drying depth, air consumption, working cycle, equipment structure, etc., each with its own characteristics.

2021-08-09

Process system


The model, quantity of air compressors, and air supply systems with different air quality and pressure should be determined based on air supply requirements, compressed air load, and technical and economic comparisons. Within the compressed air station, the number of reciprocating or screw air compressors should be 3-6 units. For air supply systems of the same quality and pressure, the number of air compressor models should not exceed two. The number of centrifugal air compressors should be 2-5 units, and the same model should be used.

2021-08-09

Ourinco

Get Quote


We will wholeheartedly provide you with high-quality products and services.

Submit