Installation of thermal alarm signals and automatic protection control for centrifugal air compressor stations
Release time:
2021-08-09
Author:
Source:
Abstract
Serial Number |
Measuring Point Name |
Thermal Alarm Signal |
Automatic Protection |
|
I. Temperature |
||||
1 |
High Exhaust Gas Temperature in Each Section |
Should |
Automatic Shutdown |
|
2 |
High Compressor Bearing Temperature |
Should |
Automatic Shutdown |
|
3 |
High/Low Lubricating Oil Tank Temperature |
Should |
Automatic Shutdown |
|
4 |
High Compressor Motor Stator Temperature |
Should |
- |
|
II. Pressure |
||||
1 |
High Exhaust Pressure in Each Cylinder Section |
Should |
- |
|
2 |
Large Air Filter Differential Pressure |
Should |
- |
|
3 |
Low Lubricating Oil Pressure |
- |
|
|
4 |
Large Oil Filter Differential Pressure |
Should |
- |
|
5 |
High/Low Air Compressor Cooling Water Inlet (After Valve) Pressure |
Should |
- |
|
6 |
Low Air Supply Pressure in the Main Pipe of the Air Compressor Station |
Should |
- |
|
III. Flow Rate |
||||
1 |
Low Air Compressor Cooling Water Inlet (After Valve) Flow Rate |
Should |
- |
|
IV. Level |
||||
1 |
Low Lubricating Oil Tank Level |
Should |
- |
|
V. Mechanical Quantity |
||||
1 |
Large Compressor Shaft Vibration |
Should |
Automatic Shutdown |
|
2 |
Large Compressor Shaft Displacement |
Should |
Automatic Shutdown |
|
3 |
Compressor Surge |
Should |
Emergency Relief |
|
VI. Others |
||||
1 |
Air Compressor Unit Control Power Failure |
Should |
- |
|
Note: 1. When the parameters of the alarm device are abnormal, an alarm should be triggered. If the alarm value continues to exceed the limit, automatic emergency relief or shutdown should be performed; |