Installation of thermal alarm signals and automatic protection control for the piston air compressor station
Release time:
2021-08-09
Author:
Source:
Abstract
Serial Number |
Measurement Point Name |
Thermal Alarm Signal |
Automatic Protection |
I. Temperature |
|||
1 |
High exhaust gas temperature of the unit cylinder |
Should |
Automatic shutdown |
2 |
Heater overheating of the adsorption air dryer with heating and regeneration |
Should |
Automatic shutdown |
3 |
Overheating of the inlet air of the regenerator of the adsorption air dryer with heating and regeneration |
Should |
Automatic shutdown |
4 |
Low evaporation temperature of the refrigeration air dryer |
Should |
Automatic shutdown |
II. Pressure |
|||
1 |
High exhaust pressure of the secondary cylinder |
Should |
— |
2 |
Low lubricating oil pressure of the air compressor transmission mechanism |
Should |
Automatic shutdown |
3 |
Low cooling water flow (after valve) or low pressure of the air compressor unit |
Should |
Automatic shutdown |
4 |
High pressure in the main water pipe of the compressed air station |
Should |
— |
5 |
High pressure in the main air supply pipe of the compressed air station |
Should |
— |
6 |
Low pressure in the main air supply pipe of the compressed air station |
Should |
— |
III. Others |
|||
1 |
Failure of the air dryer controller |
Should |
— |
2 |
Failure of the air compressor control power supply |
Should |
— |
Note: An alarm should be triggered when the parameters of the alarm device are abnormal, and automatic shutdown will occur when the alarm parameters continue to exceed the limit. |